Kits for the management of heating systems divided in different zones, heating systems with high/low temperature and heating systems with high flow rates.
Possibility of wall-hung or recessed installation thanks to the box 18 cm deep only;
Boiler maximum distance of 15 meters;
No-return valve for each zone.
Available in 5 different models:
DIM Basic
Kit for system requiring high water flow rates
DIM 2 zones
Kit for 2 zones systems
DIM 3 zones
Kit for 3 zones systems
DIM high-low temperature
Kit for mixed systems with 1 low temperature zone and 1 high temperature zone
DIM high-2 low temperature
Kit for mixed systems with 2 low temperature zone and 1 high temperature zone
Model
Height (mm)
Width (mm)
Depth (mm)
DIM basic
550
450
180
DIM 2 zones
DIM 3 zones
550
450
180
DIM high-low temperature
550
450
180
DIM high-2 low temperature
700
450
180
DIM basic
DIM 2 zones
DIM 3 zones
Maximum operating pressure
bar
3
3
3
Maximum operating temperature
°C
95
95
95
Water content
litres
4
4
4
Available head with 1000 l/h flow rate
kPa (m H2O)
41,7 (4,26)
41,7 (4,26)
41,7 (4,26)
Empty appliance weight
kg
14
16,5
19
Power Connection
V / Hz
230/50
230/50
230/50
Rated Power Input
A
0,45
0,90
1,30
Installed Electrical Power
W
100
200
300
Electrical protection index
IP
X4D
X4D
X4D
Max allowed distance boiler/DIM and DIM/DIM
m
15
15
15
DIM high-low temperature
DIM high-2 low temperature
Maximum operating pressure
bar
3
3
Maximum operating temperature
°C
95
95
Low temperature circuit temperature setting
°C
25 – 50
25 – 50
Low temperature circuit safety thermostat activation
°C
55
55
Water content
litres
4
4
Available head in high temp. circuit with 1000 l/h flow rate
kPa (m H2O)
41,7 (4,26)
43,7 (4,5)
Available head in low temp. circuit with 1000 l/h flow rate